Circutor M22348.

DHC-96 mVdc Digital Voltmeter Shunt User Manual

Model: M22348. | Brand: Circutor

1. הקדמה

The Circutor DHC-96 mVdc Digital Voltmeter Shunt (Model M22348.) is a sophisticated digital instrument panel designed for precise monitoring, regulation, and control of electrical variants and process signals. This device is capable of displaying measured electrical values or proportional values of process signals, making it suitable for a wide range of industrial and climate solar installations.

שליסל פֿעיִקייטן אַרייַננעמען:

  • הויך אַקיעראַסי אין מעזשערמאַנט.
  • Programmable measurement input.
  • Integrated relay output for control and alarm functions.
  • Universal power supply compatibility (80-270 Vca/cc and 16-36 VCC).
  • Frontal IP 54 protection for enhanced durability.
  • Galvanic insulation between external circuits.
  • Self-configurable decimal point.
  • Designed for panel installation (96 x 49 mm).
Circutor DHC-96 mVdc Digital Voltmeter Shunt with red digital display showing '0.000 A' and control buttons below.

פיגורע 1: פראָנט view of the Circutor DHC-96 mVdc Digital Voltmeter Shunt, showing its digital display and control buttons.

2. סעטאַפּ און ייַנמאָנטירונג

Proper installation is crucial for the optimal performance and longevity of your DHC-96 device. Ensure all power sources are disconnected before proceeding with installation.

2.1 פּאַנעל מאַונטינג

  • Prepare a panel cutout with dimensions of 96 x 49 mm.
  • Insert the DHC-96 unit into the cutout from the front.
  • Secure the unit using the provided mounting clips or brackets from the rear of the panel. Ensure a snug fit to maintain the IP 54 frontal protection rating.

2.2 מאַכט סופּפּלי קאַנעקשאַן

The DHC-96 supports a universal power supply. Connect the power source to the designated terminals on the rear of the unit.

  • For AC/DC power, connect to 80-270 Vca/cc terminals.
  • For DC power, connect to 16-36 VCC terminals.
  • זיכער מאַכן די ריכטיקע פּאָלאַריטעט פֿאַר גלייַך-שטראָם קאַנעקשאַנז.

2.3 Measurement Input Connection

Connect the signal source to the programmable measurement input terminals. Refer to the wiring diagram provided with your specific model for detailed connection points.

  • פֿאַר וואָלtage measurements, connect the voltagE מקור.
  • For current measurements, connect through a shunt or current transformer as appropriate for your application.
  • Ensure galvanic insulation between external circuits is maintained.

2.4 רעלע רעזולטאַט קאַנעקשאַן

The DHC-96 features two output relays for control and alarm functions. Connect these relays to your external control systems or alarm indicators as required.

  • Identify the relay output terminals.
  • Wire the relays according to your application's control logic.
  • Configure alarm delays and interlocking settings via the device's menu.

3. אַפּערייטינג ינסטרוקטיאָנס

Once installed and powered, the DHC-96 is ready for operation. The front panel features a digital display and control buttons for configuration and monitoring.

3.1 ווייַז איבערview

The digital display shows the measured electrical variant (e.g., voltage, current, frequency) or the proportional value of a process signal. The unit automatically adjusts the display based on the configured measurement type.

  • DC Systems: פעאיק צו מעסטן די וואָלומעןtage, current, frequency, and other industrial process variables.
  • AC מאָדעלס: Perform measurements in True Effective Value (TRMS).
  • דעצימאַל פונט: The decimal point is self-configurable to suit your measurement precision requirements.

3.2 קנעפּל פאַנגקשאַנז

The front panel buttons allow for navigation through menus, parameter configuration, and display adjustments. Specific button functions may vary slightly depending on the firmware version.

  • לינקס/רעכטס פײַלן (< / >): Typically used for navigating through menu options or adjusting values.
  • אַרויף/אַראָפּ פײַלן ( / ): געניצט פֿאַר פֿאַרגרעסערונגasinג/דעקרעasing values or selecting options.
  • מעניו / אַרייַן קנעפּל: Used to access the main menu, confirm selections, or save settings.
  • Escape/Back Button: Used to exit a menu or cancel an operation.

3.3 Configuration and Programming

The DHC-96 allows for programming various parameters to suit specific application needs. This includes setting the measurement input type, configuring alarm thresholds, and defining relay behaviors.

  • Access the configuration menu by pressing the Menu/Enter button.
  • נאַוויגירן דורך די מעניו אָפּציעס מיט די פייַל קנעפּלעך.
  • Select the desired parameter to modify and adjust its value.
  • Save changes before exiting the menu.
  • Refer to the detailed programming guide (if available separately) for advanced configurations.

4. וישאַלט

The DHC-96 is designed for reliable operation with minimal maintenance. Regular inspection and cleaning will help ensure its continued performance.

  • רייניקונג: Periodically clean the front panel with a soft, damp שטאָף. ניצט נישט קיין שרײַבנדיקע רייניגערס אדער סאָלווענטן, ווײַל זיי קענען שאַטן דעם עקראַן אָדערasing.
  • דורכקוק: Regularly inspect the wiring connections for any signs of wear, corrosion, or looseness. Ensure the unit is securely mounted in its panel cutout.
  • סוויווע: Ensure the operating environment remains within the specified temperature and humidity ranges to prevent damage. The IP 54 frontal protection helps against dust and splashing water, but the unit is not designed for immersion.
  • קיין באַניצער-סערוויסאַבלע פּאַרץ: The DHC-96 contains no user-serviceable parts. Do not attempt to open the casing, as this will void the warranty and may expose you to electrical hazards.

5. טראָובלעשאָאָטינג

If you encounter issues with your DHC-96, refer to the following common troubleshooting steps. For problems not listed here, contact Circutor technical support.

  • קיין אַרויסווייַז/מאַכט:
    • Check the power supply connections to ensure they are secure and correctly wired.
    • באַשטעטיקן אַז די מאַכט מקור באַנדtage is within the specified range (80-270 Vca/cc or 16-36 VCC).
    • קוקט איבער פֿאַר קיין אויסגעלאָשענע קרייז ברעיקערס אָדער צעבראָכענע פיוזן אין די מאַכט קרייז.
  • פאַלש רידינגז:
    • Ensure the measurement input is correctly connected and the signal source is active.
    • Verify that the device's measurement input type is correctly configured in the settings to match your application (e.g., voltage, current, process signal).
    • Check for any external interference or noise affecting the signal.
    • Confirm the decimal point setting is appropriate for the expected values.
  • רעליי נישט אַקטיוויִרט:
    • Check the relay output wiring for proper connection to the external control system.
    • Verify the alarm thresholds and relay logic are correctly configured in the device's settings.
    • Ensure the measured value has exceeded or fallen below the set alarm threshold.
    • Check for any configured alarm delays or interlocking conditions that might prevent immediate activation.

6. ספּעסאַפאַקיישאַנז

אַטריביוטווערט
פאַבריקאַנטסירקוטאָר
טייל נומערM22348.
נומער מאָדעל נומערM22348.
פּראָדוקט דימענשאַנז3.01 X 1.93 X 3.78 אינטשעס
פּונקט וואָג7 אונסעס
קאָלירשוואַרץ
סטיילCir
מאַכט מקורעלעקטריק
נומער פּעקל קוואַנטיטי1
באַטעריז פארלאנגט?ניין
ASINB08WL8FMDB
ערשטער דאַטע בנימצא15 אויגוסט 2023

7. וואָראַנטי און שטיצן

For detailed warranty information, please refer to the warranty card included with your product or visit the official Circutor webזייטל. גאַראַנטיע טערמינען און באדינגונגען קענען זיין אַנדערש לויט געגנט און פּראָדוקט.

For technical support, service, or inquiries regarding your DHC-96 mVdc Digital Voltmeter Shunt, please contact Circutor customer service or your authorized dealer. Provide your product model number (M22348.) and serial number (if applicable) when seeking support.

You can find more information and contact details on the official Circutor webפּלאַץ: www.circutor.com

פֿאַרבונדענע דאָקומענטן - M22348.

Preview סירקוטאָר URBAN און URBAN WB EV טשאַרדזשינג סטאַנציע מאַנואַל
באַניצער און קאָנפיגוראַציע גייד פֿאַר Circutor URBAN און URBAN WB עלעקטרישע פאָרמיטל טשאַרדזשינג סטאַנציעס, וואָס דעקט ינסטאַלירונג, אָפּעראַציע און טעכנישע ספּעסיפיקאַציעס.
Preview סירקוטאָר ליניע-TCPRS1 RS-485/RS-232 צו TCP/IP קאָנווערטער ינסטאַלירונג גייד
אינסטאַלאַציע גייד פֿאַר די סירקוטאָר ליניע-TCPRS1, אַ גייטוויי פֿאַר קאָנווערטינג RS-485 אָדער RS-232 גשמיות סביבות צו עטהערנעט און/אָדער Wi-Fi. פֿעיִקייטן Web סערווער און אַנדרויד אַפּ קאַנעקטיוויטי.
Preview סערקיוטאָר CVM-E3-MINI-ITF-WiEth מאַכט אַנאַליזער ינסטאַלירונג און טעכניש גייד
א פולשטענדיקע אינסטאַלאַציע פירער און טעכנישע ספּעציפיקאַציעס פֿאַר די CIRCUTOR CVM-E3-MINI-ITF-WiEth מאַכט אַנאַליזער. לערנט וועגן זייַנע פֿעיִקייטן, פֿאַרבינדונג דיאַגראַמען, עלעקטרישע פּאַראַמעטער מעסטונגען, און אָפּעראַציאָנעלע שליסל פֿונקציעס פֿאַר פֿאַרשידענע נעץ טיפּן.
Preview סירקוטאָר TCPRS1+ RS-485 צו TCP/IP קאָנווערטער ינסטרוקטיאָן מאַנואַל
א פולשטענדיגע אנווייזונג צום סירקוטאר TCPRS1+ RS-485 צו TCP/IP קאנווערטער, וואס באדעקט זיכערהייט, אינסטאלאציע, אפעראציע, קאמוניקאציעס (Wi-Fi, עטערנעט), טעכנישע ספעציפיקאציעס, און אויפהאלטונג.
Preview סירקוטאָר בריק LR RS-485 - LoRa™ קאָנווערטער אינסטרוקציע מאַנואַל
א פולשטענדיגע אינסטרוקציע מאנואל פארן סירקוטאר בריק LR, אן RS-485 צו LoRa™ קאנווערטער. באהאנדלט אינסטאלאציע, אפעראציע, טעכנישע אייגנשאפטן, און קאנפיגוראציע.
Preview Circutor CVM-C5 Series Power Analyzer Instruction Manual
Instruction manual for Circutor CVM-C5 series power analyzers, including models CVM-C5-ITF-485, CVM-C5-MC-485, and CVM-C5-mV-485. Provides detailed information on installation, operation, programming, and technical specifications.