Simplex S4099-9006

Simplex 4099-9006 Double Action, Push Pull Down Fire Alarm Station

מאָדעל: S4099-9006

1. הקדמה

This manual provides comprehensive instructions for the installation, operation, and maintenance of the Simplex 4099-9006 Double Action, Push Pull Down Fire Alarm Station. This device is designed to initiate a fire alarm signal when manually activated, contributing to the overall safety and security of a building's occupants.

The Simplex 4099-9006 is an IDNet addressable manual pull station with an integrated LED indicator, ensuring reliable communication within compatible fire alarm systems.

2. זיכערקייַט אינפֿאָרמאַציע

WARNING: Installation and servicing of this device must be performed by qualified personnel only, in accordance with all local and national electrical codes, and the National Fire Alarm and Signaling Code (NFPA 72).

  • Always disconnect power to the fire alarm control panel before installing or servicing the pull station.
  • פאַרזיכערן געהעריק גראַונדינג צו פאַרמייַדן עלעקטריקאַל קלאַפּ.
  • Do not paint over the pull station or obstruct its operation.
  • Test the pull station regularly as part of a comprehensive fire alarm system testing schedule.
  • This device is not intended for outdoor use unless specifically rated for such environments.

3. פּראָדוקט איבערview

The Simplex 4099-9006 is a robust, red-colored manual fire alarm pull station featuring a double-action mechanism (push then pull). It includes an integrated LED indicator for status feedback.

Simplex 4099-9006 Double Action Fire Alarm Pull Station with installation instructions

Figure 3.1: Simplex 4099-9006 Double Action Fire Alarm Pull Station. This image displays the front of the red pull station with "FIRE ALARM" and "PUSH PULL DOWN" labels, alongside a detailed instruction sheet for installation and mounting, and a small bag of mounting hardware.

די הויפּט קאַמפּאָונאַנץ אַרייַננעמען:

  • אַקטיוואַציע שעפּן: The "PUSH PULL DOWN" mechanism used to initiate an alarm.
  • LED ינדיקאַטאָר: Provides visual status of the device (e.g., normal, alarm, trouble).
  • טערמינאַל בלאָק: For connecting to the fire alarm control panel's IDNet circuit.
  • Mounting Plate/Housing: Secures the device to a standard electrical box or surface.

4. אויפשטעלן און אינסטאַלירן

The Simplex 4099-9006 pull station can be installed using either single-gang or two-part mounting methods, typically on a standard 4-inch square electrical box (not supplied).

4.1 פאַר-ינסטאַלירונג טשעקס

  • Verify that the fire alarm control panel is powered off.
  • Ensure the mounting location is clean, dry, and meets local code requirements for height and accessibility.
  • Confirm all necessary tools and hardware are available (e.g., screwdriver, wire strippers, mounting screws).

4.2 Mounting Procedures

Refer to the installation diagrams provided with the product and shown in Figure 3.1 for visual guidance.

4.2.1 Single-Gang Mounting

  1. Secure the pull station directly to a standard single-gang electrical box.
  2. Ensure the device is flush with the wall surface.

4.2.2 Two-Part Mounting

  1. Install the backbox or mounting plate first, typically a 4-inch square electrical box.
  2. Mount the pull station assembly onto the installed backbox.
  3. This method may be used for flush trim or surface mounting applications.

4.3 וויירינג

The 4099-9006 is an IDNet addressable device. Connect the pull station to the IDNet circuit of the fire alarm control panel using appropriate gauge wiring, following the wiring diagram provided on the device or in its specific installation sheet. Ensure polarity is correct.

  • Connect the incoming and outgoing IDNet circuit wires to the designated terminals.
  • פאַרזיכערן אַז אַלע קאַנעקשאַנז זענען זיכער און פריי פון קורצע הייזלעך.

4.4 נאָך-אינסטאַלאַציע

  • Once installed and wired, restore power to the fire alarm control panel.
  • Verify the LED indicator on the pull station shows a normal operating status (typically a slow flash).
  • Perform a functional test of the pull station as described in the "Operating Instructions" section.

5. אַפּערייטינג ינסטרוקטיאָנס

The Simplex 4099-9006 features a double-action activation mechanism to prevent accidental alarms.

5.1 Activating the Alarm

  1. שטופּן: Firmly push the "PUSH" bar located at the top of the activation handle.
  2. PULL DOWN: Once the "PUSH" bar is depressed, pull the handle "PULL DOWN" until it latches in the alarm position.
  3. Upon activation, the pull station will send an alarm signal to the fire alarm control panel, and the integrated LED will illuminate steadily (or change to a rapid flash, depending on system programming) to indicate an alarm state.

5.2 איבערשטעלן די פּול סטאנציע

To reset the pull station after an alarm, a special key (not included with this specific model, as indicated by "No Key" in the product title, implying a different reset mechanism or system-level reset) or tool is typically required to return the handle to its normal, non-alarm position. For the 4099-9006, the reset mechanism is internal and does not require a key. Simply push the handle back into its original position. The fire alarm control panel must also be reset to clear the alarm condition from the system.

6. וישאַלט

Regular maintenance ensures the reliable operation of your Simplex 4099-9006 pull station. All maintenance should be performed by qualified personnel.

6.1 רוטינע קאָנטראָלן

  • Visual Inspection (Monthly): Check for any physical damage, obstructions, or signs of tampering. Ensure the pull station is clean and clearly visible.
  • LED Status (Monthly): Verify the LED indicator is showing a normal operating status (e.g., slow flash).

6.2 Functional Testing (Annually or as per local codes)

Functional testing should be conducted by a certified fire alarm technician.

  1. Notify building occupants and the monitoring station before testing.
  2. Activate the pull station as described in "Operating Instructions".
  3. Verify that the fire alarm control panel receives the alarm signal and initiates appropriate responses (e.g., sounding alarms, notifying monitoring station).
  4. Reset the pull station and the fire alarm control panel.
  5. Confirm the pull station returns to a normal operating state.

6.3 רייניקונג

Clean the exterior of the pull station with a soft, damp שטאָף. ניצט נישט קיין שרײַבנדיקע רייניגערס אדער סאָלווענטן, ווײַל די קענען שאַטן די ענדיקונג אדער אינעווייניקסטע קאָמפּאָנענטן.

7. טראָובלעשאָאָטינג

This section addresses common issues you might encounter with the Simplex 4099-9006 pull station. For complex issues, contact a qualified fire alarm technician.

פּראָבלעםמעגלעך סיבהלייזונג
Pull Station does not activate alarm.Incorrect activation procedure; wiring issue; device fault; control panel issue.Ensure proper push-then-pull action. Check wiring connections. Verify control panel status. Contact technician if problem persists.
LED indicator is off or shows trouble.No power; wiring fault; device fault; control panel trouble.Check power to the control panel. Inspect wiring for breaks or shorts. Consult control panel manual for trouble codes. Contact technician.
פאלשע שרעק.Accidental activation; faulty device; wiring issue.Reset the pull station and control panel. Inspect for physical damage or obstructions. If recurring, contact technician.
Pull station handle does not reset.Internal mechanism issue; debris.Ensure no debris is obstructing the mechanism. Gently attempt to push the handle back. If it remains stuck, the unit may need replacement.

8. ספּעסאַפאַקיישאַנז

שטריךדעטאַל
מאָדעל נומערS4099-9006
פּראָדוקט טיפּDouble Action Manual Fire Alarm Pull Station
סאָרטסימפּלעקס
פאַבריקאַנטSIMPLEX Grinnell
קאָליררויט
אַקטאַוויישאַן אופֿןPush then Pull Down
Key Requirement for ResetNo Key Required (Internal Reset)
קאַנעקטיוויטיIDNet Addressable
ינטעגראַטעד פֿעיִקייטןגעפירט ינדיקאַטאָר
פּונקט וואָג0.5 פונט (אומגעפער 8 אונסעס)
פּראָדוקט דימענשאַנז6 X 6 X 4 אינטשעס (בעערעך)
UPC643485653004
ערשטער דאַטע בנימצא21טן דעצעמבער 2015
Simplex 4099-9006 product packaging boxSimplex 4099-9006 product packaging box with PID and Part No.

Figure 8.1: Product packaging for the Simplex 4099-9006, showing the brown cardboard box with product identification labels. The labels confirm PID 4099-9006 and Part No. 06501211.

9. וואָראַנטי & שטיצן

9.1 וואָראַנטי אינפֿאָרמאַציע

This Simplex product is typically covered by a manufacturer's warranty against defects in materials and workmanship. Specific warranty terms and duration may vary. Please refer to the original purchase documentation or contact Simplex customer service for detailed warranty information.

Note: The product listing mentions "12 months warranty" and "30 days return if not satisfied". This information is from a third-party seller and may not reflect the official manufacturer's warranty. Always verify with the manufacturer.

9.2 טעכניש שטיצן

For technical assistance, installation guidance, or troubleshooting beyond the scope of this manual, please contact a certified fire alarm technician or the manufacturer directly.

Simplex Customer Support: Please visit the official SimplexGrinnell webזייטל אדער זעט אייער פּראָדוקט פּאַקאַדזשינג פֿאַר קאָנטאַקט דעטאַילס.

פֿאַר אַלגעמיינע פֿראַגעס, קענט איר אויך זיך ווענדן צו די Simplex brand page on Amazon.

פֿאַרבונדענע דאָקומענטן - S4099-9006

Preview סימפּלעקס IDNet/MAPNET II אַדרעסירבארע מאַנועלע פייער אַלאַרם סטאַנציעס - פּראָדוקט דאַטן
דעטאַלירטע אינפֿאָרמאַציע וועגן סימפּלעקס 4099 סעריע אַדרעסירבארע מאַנועלע פֿײַער אַלאַרם סטאַנציעס, קאָמפּאַטיבל מיט IDNet און MAPNET II סיסטעמען. פֿעיִקייטן, ספּעציפֿיקאַציעס, מאַונטינג אָפּציעס, און פּראָדוקט סעלעקציע פֿאַר פֿאַרשידענע מאָדעלן, אַרייַנגערעכנט איין-אַקציע, טאָפּל-אַקציע (ברעכגלאַס און שטופּ), און NO GRIP אָפּציעס. קאָמפּליאַנט מיט ADA רעקווירעמענץ און ליסטעד דורך UL, ULC, FM, און CSFM.
Preview סימפּלעקס אַדרעסאַבלע מאַנועלע סטאַנציעס: IDNet/MAPNET II פּעריפעראַלז
אויספאָרשן סימפּלעקס אַדרעסאַבלע מאַנועלע פייער אַלאַרם סטאַנציעס, דעטאַלירן זייערע פֿעיִקייטן, איין/טאָפּל אַקציע טיפּן, NO GRIP אָפּציעס, און קאָמפּאַטאַביליטי מיט IDNet/MAPNET II סיסטעמען. כולל מאָונטינג און ספּעציפיקאַציע אינפֿאָרמאַציע.
Preview סימפּלעקס 2099 סעריע איין און טאָפּל אַקציע מאַנועלע פייער אַלאַרם סטאַנציעס דאַטאַבלאַט
דאטן-בלאט פאר סימפלעקס 2099 סעריע נישט-קאדירטע, נישט-אדרעסירבארע מאנועלע פייער אלארם ציען סטאנציעס. דעקט אייגנשאפטן, אפעראציע טיפן, אפליקאציע רעפערענצן, פראדוקט אויסוואל, מאונטינג אפציעס, און ספעציפיקאציעס.
Preview סימפּלעקס 4010עס: סיסטעם פון יקסטינגשאַן אָטאַמאַטיק פֿאַר גיקלערז
גייד טעכניק סימפּלעקס 4010עס דעטאַילאַנט די מאַדזשולז פון קאַמאַנדז פֿאַר די סיסטעם פון יקסטינגשאַן אָטאַמאַטיק פֿאַר גיקלאָרס, קאָוווראַנט ליי מאָדעס און פּרעווענטיף, מיט ספּעסאַפאַקיישאַנז, כאָומאַלאַדזשיז און סטשעמאַס דע קאַבלע.
Preview סימפּלעקס 4004 פייער אַלאַרם קאָנטראָל פּאַנעל: ינסטאַלירונג און אָפּעראַציע אינסטרוקציעס
א פולשטענדיקע אנווייזונג פארן אינסטאלירן, אפערירן און פראגראמירן דעם סימפלעקס 4004 פייער אלארם קאנטראל פאנעל (FACP), אריינגערעכנט סיסטעם איבערview, רעקווייערמענץ, וויירינג, מאָדול באַשרייַבונגען, און טראָובלעשאָאָטינג.
Preview סימפּלעקס 4010ES פייער קאָנטראָל אַפּאַראַט דאַטאַבלאַט: אויטאָמאַטישע לעשער, דעלאַזש און פּרעאַקשאַן ספּרינקלער סיסטעמען
טעכנישע דאטן-בלאט פארן סימפלעקס 4010ES פייער קאנטראל איינהייט, וואס דעטאלירט זיינע מעגלעכקייטן פאר אויטאמאטישע אויסלעשן, איבערפלוסן, און פאר-אקציע שפרינקלער סיסטעם.asinג קאָנטראָל. כולל פֿעיִקייטן, ספּעציפֿיקאַציעס, אַגענטור ליסטינגס, און קאָמפּאַטיבלע קאָמפּאָנענטן.